HP to Amps Calculator

Convert motor horsepower to current using supply voltage, efficiency, power factor, and phase.

Horsepower to Current
Choose the electrical supply and enter the motor's operating values.

About Horsepower to Amps Conversion

Horsepower describes a rate of mechanical work, while amperes describe electrical current. A motor's nameplate horsepower is mechanical output power, so current cannot be found from horsepower alone. The electrical supply must deliver additional power to cover motor losses, and alternating-current systems also require power factor. This calculator begins with the common conversion of one mechanical horsepower to 746 watts, then accounts for voltage, efficiency, supply type, and power factor. For a DC motor, estimated current equals output watts divided by voltage and decimal efficiency. For single-phase AC, the denominator also includes power factor. For balanced three-phase AC, it includes power factor and the square root of three. Efficiency must be entered as a percentage, such as 90 for a motor that converts 90 percent of electrical input into mechanical output. Power factor is a decimal between zero and one and represents how effectively apparent AC power becomes real power. The result is an engineering estimate of current at the entered operating point. Actual motor current varies with load, speed, design, temperature, supply quality, and manufacturer. Starting or locked-rotor current can be several times greater than normal full-load current, so this result must not be used as a direct substitute for conductor, disconnect, overload, or short-circuit protection requirements. Electrical codes often provide standardized full-load-current tables that intentionally differ from a calculation based on nominal efficiency and power factor. Use line-to-line voltage for a three-phase calculation and the operating supply voltage for DC or single-phase equipment. Obtain efficiency and power factor from the motor data sheet at the relevant load whenever possible. Small motors and lightly loaded motors may have substantially lower efficiency or power factor than assumed defaults. Also distinguish mechanical horsepower from electrical horsepower conventions and metric horsepower; this tool uses 746 watts per mechanical horsepower. This conversion is useful for early power-system estimates, comparing motors, checking whether a measured running current is plausible, and understanding the role of phase and losses. Final equipment selection should follow the motor nameplate, manufacturer instructions, applicable electrical code, service factor, duty cycle, ambient conditions, and a qualified electrical design.

HP to Amps Examples

Motor and supplyEstimated currentUse case
5 HP, 230 V, 90%, PF 0.85, single phase21.2 ASmall single-phase motor
10 HP, 460 V, 92%, PF 0.88, three phase11.56 AIndustrial three-phase motor
2 HP, 120 V, 85%, DC14.63 ADC drive estimate

How to Convert HP to Amps

  1. Choose DC, single-phase AC, or three-phase AC to apply the correct power equation.
  2. Enter the motor's mechanical horsepower rating and operating voltage.
  3. Enter efficiency as a percentage and, for AC, enter the decimal power factor.
  4. Select Convert HP to Amps and use the result as an operating-current estimate.

Frequently Asked Questions

Why are voltage and phase required?

Current depends on how electrical power is delivered, not just on mechanical output. Single-phase, three-phase, and DC systems use different power relationships.

Why does lower efficiency increase current?

A less efficient motor needs more electrical input power to produce the same shaft output. At unchanged voltage and power factor, that additional input requires more current.

What power factor should I use?

Use the manufacturer's value at the expected load whenever available. If it is unknown, an assumed value provides only a rough estimate because power factor changes with motor design and loading.

Is this the motor starting current?

No, the calculation estimates steady operating current at the stated conditions. Starting current can be several times higher and requires motor-specific data.

Can I size wires and breakers from this result?

Do not use this estimate alone for final electrical protection or conductor sizing. Follow applicable code tables, nameplate ratings, duty requirements, and professional design practices.