Wire Size Calculator
Estimate the minimum copper conductor area and AWG size needed to satisfy a circuit voltage-drop target.
About wire size and voltage drop
Wire sizing examples
| Inputs | Calculated output | Application |
|---|---|---|
| 20 A, 120 V, 50 ft, 3% | 2.92 mm²; 12 AWG | General branch-circuit voltage-drop estimate |
| 30 A, 240 V, 100 ft, 3% | 4.38 mm²; 10 AWG | Higher voltage permits a larger absolute drop |
| 10 A, 12 V, 20 ft, 3% | 5.84 mm²; 9 AWG | Low-voltage systems are sensitive to cable loss |
How to use the calculator
- Enter the maximum current expected at the load.
- Enter the nominal circuit voltage.
- Measure the one-way source-to-load distance in feet.
- Choose the maximum acceptable voltage-drop percentage.
- Select Calculate Wire Size and compare the result with code ampacity requirements.
Frequently asked questions
Why does distance have such a large effect?
Resistance increases directly with conductor length. A longer run therefore needs more cross-sectional area to maintain the same voltage drop.
What voltage-drop percentage should I use?
Three percent is a common design target for a branch circuit, but it is not universal. Follow equipment requirements and the electrical rules that apply to the installation.
Does this calculator check ampacity?
No. It sizes copper for voltage drop only, so the final conductor must also meet or exceed code ampacity and temperature requirements.
Why is the AWG result rounded down numerically?
Lower AWG numbers identify larger conductors. Rounding the mathematical gauge down selects the next standard size with at least the required area.
Can I use this recommendation for aluminum?
No, the formula uses copper resistivity. Aluminum needs a larger area and must be evaluated with aluminum properties, terminals, and code tables.