Air Changes Per Hour Calculator
Calculate ACH from room dimensions and HVAC airflow.
About air changes per hour
ACH examples
| Room and airflow | ACH | Typical use |
|---|---|---|
| 20 ft × 15 ft × 10 ft; 300 CFM | 6.00 ACH | Medium office or workroom |
| 10 ft × 10 ft × 8 ft; 80 CFM | 6.00 ACH | Small enclosed room |
| 30 ft × 20 ft × 12 ft; 600 CFM | 5.00 ACH | Large shared space |
How to calculate ACH
- Measure the inside length, width, and average height of the room in feet.
- Obtain the delivered supply or exhaust airflow in cubic feet per minute.
- Enter all four values and select Calculate ACH.
- Compare the result with the requirement that applies to the room and occupancy.
Frequently asked questions
What does 6 ACH mean?
It means the hourly airflow is six times the room's calculated volume. It does not mean every air molecule is replaced exactly six times because real mixing is imperfect.
What formula does the calculator use?
ACH equals CFM multiplied by 60, divided by room volume in cubic feet. Room volume equals length multiplied by width multiplied by height.
Can I use exhaust fan airflow?
Yes, when the exhaust airflow represents the air removed from the measured room. Make-up air and pressure balance still need separate consideration.
Does a higher ACH always mean better air quality?
Not necessarily, because source control, outdoor-air quality, filtration, and distribution also matter. Excess airflow can also increase noise and energy use.
Can ACH prove building-code compliance?
ACH can support a ventilation check, but many codes use occupancy-based outdoor airflow and other requirements. Consult the governing code and a qualified HVAC professional.