KVA Calculator

Calculate apparent, real, and reactive power for a single-phase load.

Electrical power calculator
Enter RMS voltage, RMS current, and power factor for a single-phase AC circuit.

About kVA and AC power

Kilovolt-amperes, abbreviated kVA, measure apparent power in an alternating-current circuit. Apparent power combines the voltage and current delivered by a source without assuming that they peak at the same time. For a single-phase load, apparent power in kVA equals RMS voltage times RMS current divided by one thousand. The value describes the total electrical capacity that conductors, transformers, generators, switches, and protection equipment may need to carry. Kilowatts measure real power, the portion converted into useful work, heat, light, or motion. Real power equals apparent power multiplied by power factor. Power factor ranges from zero to one and describes how effectively current contributes to useful energy transfer. A resistive heater can approach unity power factor, while motors, transformers, and electronic loads may draw current that is shifted or distorted. A 10 kVA load at 0.8 power factor therefore uses 8 kW of real power. Reactive power, expressed in kVAR, represents energy exchanged with magnetic and electric fields. For the simplified power triangle used here, reactive power equals apparent power multiplied by the square root of one minus power factor squared. Real power, reactive power, and apparent power form a right triangle: kVA squared equals kW squared plus kVAR squared. This relationship is appropriate when a single aggregate power factor accurately represents the load. Use RMS voltage and current measured under the same operating condition. This calculator is specifically configured for single-phase power. Three-phase balanced systems require an additional square-root-of-three factor when line-to-line voltage and line current are used. Also distinguish kVA from kW when sizing equipment: a generator or transformer rating is often limited by apparent power and current even when the connected load consumes fewer kilowatts. The calculated values support preliminary sizing, classroom analysis, and quick field checks. Final electrical designs must also consider startup current, harmonics, duty cycle, ambient conditions, code requirements, conductor ampacity, protective devices, and manufacturer ratings.

KVA calculation examples

Voltage, current, power factorApparent, real, reactive power
230 V, 10 A, PF 0.82.3 kVA, 1.84 kW, 1.38 kVAR
120 V, 5 A, PF 10.6 kVA, 0.6 kW, 0 kVAR
240 V, 20 A, PF 0.64.8 kVA, 2.88 kW, 3.84 kVAR

How to use the KVA calculator

  1. Enter the single-phase RMS voltage in volts.
  2. Enter the RMS load current in amperes.
  3. Enter the load power factor as a decimal from zero to one.
  4. Calculate and compare apparent, real, and reactive power.

Frequently asked questions

What is the difference between kVA and kW?

KVA measures total apparent power, while kW measures power converted into useful work. They are equal only when power factor is one.

What is power factor?

Power factor is the ratio of real power to apparent power. A higher value means the supplied current is used more effectively.

Can I use this for three-phase power?

This implementation calculates a single-phase circuit. A balanced three-phase line calculation normally includes a square-root-of-three multiplier.

Why are transformers rated in kVA?

Transformer heating is strongly related to voltage and current rather than the load's power factor. An apparent-power rating therefore represents its electrical loading more directly.

Can reactive power be zero?

Yes, the simplified reactive component is zero at unity power factor. The apparent and real power values are then equal.